Pauwels International NV

Package Substations










Pauwels International - MiniSubs

MiniSub for UK requirements

UK Standard Range
kVA Phases Voltage ratio
200 3 11000/433
315 3 11000/433









 Features
  • Low profile
  • 3 outgoing ways
  • Flush cover door lock
  • Tamper proof
  • E Coat paint system
  • Simple foundation
  • HV isolation facility
  • LV generator connectivity
The Pauwels MiniSub is an evolution and development of the MicroSub design intended to replace the ESI type Minisub with a more cost effective and compact system. Using a similar arrangement to the USA type Padmount transformer the Pauwels MiniSub range is fitted with HV Bay-O-Net™ withdrawable HV fuses in combination with HRC backup fuses in-tank as standard and a 3 way 3 phase outgoing fuse distribution unit. Alternative LV systems include LV circuit breakers or fuse switch units. HV termination can be by plug in bushings or by conventional dry type cable box. The unit shown above was developed with respect to the defined needs of a major UK utility and their operational systems. Other UK utilities are also now using this type of unit.

The original ESI type Minisub used an oil fuse switch for HV switching and protection. While HV switching has obvious advantages the fact is that in many applications the switching facility is only rarely used, if at all during the lifetime of the unit. The Pauwels MiniSub keeps cost and size down by not having these rarely used HV switching facilities. HV isolation can be achieved by withdrawing the HV fuses while the unit is de-energised. Temporary generation can be connected via the LV distribution unit.
Mini padmount design

The MiniSub, as the name suggests is a little bigger than our MicroSub unit but still a very compact product. Double front access doors enable access to the HV connection box and the LV equipment. Once again, in the unlikely event of problems with the transformer the ease of installation and handling means that a replacement unit can be quickly fitted to minimise loss of supply for customers. The faulty unit is then taken away for service off site. Back to Package Subs